product_Banner

EM131 Analog Input (131-0HC10)

Analog Input Module, 4AI×12BIT, Voltage or Current Input,Isolation​

Order No.:CTS7 131-0HC10

Specification:EM131 Analog Input,4AI×12BIT

Product Description

Order data

Specification
Order No.
CTSC-100 EM131 Analog Input Module, 4AI×12BIT, Voltage or Current Input, Isolation
CTS7 131-0HC10


Technical Spec

Performance Parameters

SpecificationEM131, 4 AI×12BIT
Physical Features
Dimensions(W×H×D)71.2×80×62mm
Power Loss(dissipation)2W
Power Consumption
From +5V(from I/O bus)34 mA
From L+40 mA
L+  voltage range,class 2 or DC sensor supply20.4~28.8V DC
LED indicator24 VDC Power Supply  Good
           ON = no fault,
           OFF = no 24 VDC power
Analog Input Feature 
Number of analog input points4 points
Isolation(field side to logic circuit)no
input typeDifferential
Input Range
Voltage(unipolar)0~10V, 0~5V
        Voltage(bipolar)±5V, ±2.5V
        Current0~20 mA
Data Range
        Unipolar, full-scale range0~32000
        Bipolar, full-scale range-32000~32000
Input Resolution
        Voltage(unipolar)
2.5 mV (0~10V)
1.25 mV (0~5V)
        Voltage(bipolar)
2.5 mV (±5V)
1.25 mV (±2.5V)
        Current5μA (0~20mA)
Analog to digital conversion time<300μs
Analog input step response100ms
Common mode rejection40dB,DC to 60Hz
Common mode voltageSignal voltage + Common mode voltage < 12V
Input Impedance≥10MΩ
Input filter attenuation-3db @ 3.1kHz
Maximum input voltage30V
Maximum input current30mA
ADC resolution12BIT

Calibration and Configuration

Location of the calibration and configuration switch

Input Calibration

The calibration adjustment will affect the instrumentation amplifier stage which follows the analog multiplexer. so the calibration affects all user input channels. Variations exist in the component parameters of each input circuit before the analog multiplexer will cause slight differences in the reading values between different channels connected to the same input signal even after calibration.

If need to acquire the specifications contained in this data sheet, may be you need to enable analog input filters for all inputs of the module. Please select 64 or more samples to calculate the average value.
To calibrate the input, please use the following steps.
1.       Turn off the power to the module, select the desired input range.
2.       Turn on the power to the CPU and module. Allow the module to stabilize for at least 15 minutes.
3.       Using a transmitter, a voltage source, or a current source, connect a full-scale value signal to one of the input channels, read the value reported to the CPU.
4.       Adjust the GAIN potentiometer until the reading is 32000.

 

Configuration

Table 1 shows how to configure the EM 131 module using the configuration DIP switches. Switches 1, 2, and 3 select the analog input range. All inputs are set to the same analog input range. In this table, ON is closed, and OFF is open. (SW4 to SW6 should be set to the OFF position)
Table 1   EM 131 Configuration Switch Table to select Analog Input Range
UnipolarFull-S cale InputResolution
SW1SW2SW3
ONOFFON0 to 10V2.5mV
ONOFF0 to 5V1.25mV
0 to 20mA5 uA
BipolarFull-Scale InputResolution
SW1SW2SW3
OFFOFFON± 5 V2.5mV
ONOFF± 2.5 V

1.25mV
             

Input Data Word Format

 
Note
The 12 bits readings of the analog-to-digital converter (ADC) are left-justified in the input data word format. The MSB is the sign bit: zero indicates a positive data word value. In unipolar format, the three trailing zeros cause the data word to be changed by a count of eight for each one-count change in the ADC value. In bipolar format, the four trailing zeros cause the data word to be changed by a count of sixteen for each one count change in the ADC value.
 
Installation

Size  Diagram:


Wiring Diagram

       


Return

Follow us

9F, Block A Building 6, Shenzhen International Innovation Valley, Dashi 1st Road, Nanshan District, Shenzhen

400-700-4858
0755-86226822

market@co-trust.com

Copyright COTRUST TECHNOLOGIES CO., LTD. 粤ICP备13051915号-2