- Product Description
-
1. The PROFINET bus communicates at a rate of 100 Mb Ps, and the communication distance from station to station can be up to 100 meters (100BASE-TX);
2, topological structure support star, tree, linear, ring structure;
3. Each slave station is allowed to expand 8 I/O modules (digital quantity module, analog quantity module, temperature module, HSC, HSP, excluding CAN module /ECT slave station module).
4. Supported Siemens PROFINET master station, including Siemens S7-300, Siemens S7-400, Siemens S7-1200, Siemens S7-1500;
5. Configuration software TIA Portal V13 and higher.
- Technical Spec
-
Physical properties
Size(W×H×D)
34×115×100mm mm
Power loss
Rated input voltage
24V DC
Input voltage range
20.4V~28.8V DC
Input current
0.8A
Bus power supply voltage
+5V DC
Bus supply current
1.6A
Isolation
External power supply is isolated from system power supply
Power protection
The power supply end provides the reverse connection protection function and the surge absorption function
LED indicator characteristics
24V power indicator (green)
ON = 24VDC power supply is normal
OFF = No 24VDC power supply
SF indicator light (red)
ON = extended I/O bus failure or PROFINET module failure
OFF = No error
BF indicator light (red)
ON = PROFINET bus communication failure (no connection to switch, no network detected)
Blinking=Inconsistent hardware configuration
OFF = No error
MT indicator light (yellow)(Maintenance indicator light)
Reserved
Indicator light (green)
ON = There is a connection to the switch /PN master
OFF =No connection to switch /PN master
Indicator light (yellow)
ON = data receiving and receiving to switch /PN master station
OFF = No data transceiver to switch /PN master station
EetendI /O capabilities
Maximum number of modules supported per slave
8(can be added digital , analog and temperature module, HSC,HSP module, other types of module are not included)
Protocol type
CTH300 PLC custom 55MHz bus protocol
Topology
Support star, tree, linear, ring
PROFINET communication port
Communication port
1 dual RJ45 port
Data transmission rate
Ethernet with a transmission rate of 10Mbps
The PROFINET transmission rate is 100Mbps, full duplex
Supported Ethernet services
Ping, ARP, Network Diagnostic (SNMP)/MIB-2, LLDP
Sending cycle
250us~4ms
Third-party PROFINET master station
Support
Longest communication distance from station to station
100m(100BASE-TX)
Topology
Supports star, tree, linear and ring topologies
Isolation
Communication port isolation
Hardware configuration function
Import file type
Profinet GDS file XML format
Third-party PN master station
The addition of the CTH3 PNT-000S1 module supports the expansion of 8 slots
Expansion module can add digital, analog and temperature module, HSC,HSP module, other types of module are not included
- Installation