CTH300 TC Input Module(AIT-04,AIT-08)

Thermocouple Input Module,4/8*TC,Isolation,16bit precision

Order No.:CTH3 AIT-040S1/CTH3 AIT-080S1

Specification:Thermocouple Input Module,4/8*TC,Isolation,16bit precision

Product Description

Oder Data

Product Name

Specification

Order No.

AIT-04 

Thermocouple Input , 4-channel TC, isolation 16bit precision

CTH3 AIT-040S1

AIT-08 

Thermocouple Input , 8-channel TC, isolation 16bit precision

CTH3 AIT-080S1

 

 


Technical Spec

Performance Parameters

1.General Characteristics

 

Characteristics

AIT-040S1

AIT-080S1

Physical Characteristics

Dimension(W×H×D

34×115×100 mm

Power Characteristics

Rated input voltage

24V DC

Input voltage range

20.4V~28.8V DC

Input current

50mA

Reverse polarity protection

Yes

Bus power voltage

+5V DC

Bus power current

50mA

LED lights Diagnostics

24V power LED

On:24VDC normal power;Off:No 24VDC power supply

SF LED

On:system-down;Off:no error,flash:iInput signal error

2. Input Characteristics

Input type

Suspension-type thermocouple

Number of inputs

4

8

Wiring

-

Input Range

Thermocouple type (choose one): 

S, T, R, E, N, K, J 

Voltage range: ± 80mV 

Default: K

Isolation 

Field to Logic 

Site to 24VDC 

24VDC to logic

 

500VAC

500VAC

500VAC

Common Mode Rejection

>100dB@120VAC

Input resolution 

Temperature 

Voltage 

Resistance

 

 0.1℃/0.1℉

-

15 + sign bit

Measuring principle

Sigma-Delta

Module update frequency (all channels)

4 channel support 8Hz, 4Hz, 2Hz, 1Hz configured,  default : 2Hz all channels

8 channel support 4Hz、2Hz、1Hz、0.5Hz configured,  default : 2Hz all channels

length of wire to sensor

Max,100m

Wire loop resistance

100Ω

Noise suppression

85dB@50Hz/60Hz/400Hz

Data word format

电压:-27648~+27648

Input impedance

>10MΩ

Maximum input voltage

Inputs can support a maximum voltage to 30V DC of misconnection

Resolution

15bit + sign bit

Input filter attenuation

-3dB@21KHz

Basic error

0.1% Fs (voltage)

Repeatability

0.05%Fs

Cold junction compensation

Can be configured, default :yes

Cold junction error

±1.5℃

Temperature Unit

Celsius / Fahrenheit can be configured,  default Celsius

Break detection

Can be configured, default :yes

Support both positive and negative directions calibration, default positive calibration

Diagnostic 

 Break 

No module supply

 

 

32767(positive calibration),-32768( negative calibration)

32766

With integrated PID control function

no

 

Installation
  1. Wiring Diagram

  2. 1. AIT-040S1 

  3. AIT04.jpg

  4.  

  5. 2. AIT-080S1

AIT08.jpg


 

Return