- Product Description
-
① Profinet bus communication rate 100Mbps,the maximum communication distance up to 100m between two slave module(100BASE-TX).
② The topological structure support star,tree,linear,ring structure.
③ Each slave module allow to extend 8 I/O module(digital module,analog module,temperature module,PID module.but CAN module,
motion control module,weighting module are not include).
④ Support Siemens Profinet master station,Siemens S7-300,Siemens S7-1200,Siemens S7-1500.
⑤ Programming software TIA Portal V13 and above version.
- Technical Spec
-
Physical Features
Dimension(W×H×D)
71×80×62 mm
Power Consumption
Rated voltage input
24V DC
Voltage range
20.4V~28.8V DC
Current input
0.8A
Bus power voltage
+5V DC
Bus power current
1.1A
Isolation
The external power supply is isolated from the system power supply
Power protection
provides reverse connection protection and surge absorption
LED Indicator
24V Indicator(Green)
ON = 24VDC power
OFF = 24VDC no power
SF Indicator(red)
ON = extend I/O Bus failure or PROFINET module failure
OFF = no fault
BF Indicator(red)
ON = PROFINET Bus communication failure (no connection to switch, no network detected)
Blinking=Hardware configuration is inconsistent
OFF = no fault
MT Indicator(yellow)
(maintenance indicator )
ON = Loss of synchronization
OFF = no fault
P1R/P2Rport Indicator(green)
ON = There is a connection to the switch /PN master station
OFF = There is no a connection to the switch /PN master station
P1R/P2Rport Indicator(yellow)
ON = received data
OFF = no received data
Expansion I/O
Maximum support module
8(digital module、analog module、temperature module and PID module,other moudle is not included)
Protocol
CTSC-200 PLC 4MHZ Bus protocol
Maximum IO each station
Analog IO up to 64AI/32AQ
Digital IO up to 256DI/256DQ
Topological structure
support star,tree,linear,ring structure.
PROFINET port
Communication port
1*dual RJ45 port
Data transmission rate
Ethernet speed rate 10Mbps
PROFINET speed rate100Mbps
Support Ethernet
ping、arp、(SNMP)/MIB-2、LLDP
Send
250us~4ms
The third part PROFINET master station
Support
Maximum distance
100m(100BASE-TX)
Topological structure
support star,tree,linear,ring structure.
Isolation
Communication port isolation
Hardware configuration function
File type
PROFINET GDS file XML format
The third part PN master station
Add CTS7 277-0PN32 then support 8pcs expansion model
digital module、analog module、temperature module and PID module,other moudle is not included
- Installation