SM231 High precision analog current input, 8 channels (231-1HF32)

Order No.:CTH2 231-1HF32

Specification:SM231 High precision analog current input,8*16BIT, optocoupling isolation

Product Description

Order Data

Model No.DescriptionOrder No.
SM231SM231 High precision analog current input,8*16BIT, optocoupling isolationCTH2 231-1HF32


Technical Spec

Performance Parameters

Physical Features 

Dimension(W×H×D)

120.5×80×62mm

Weight

210g

Power loss

Bus 5VDC

25 mA

L+

31mA

L+ coil voltage range

20.428.8V DC

Power loss

1 W

Analog Input Features 

Analog input 

8

Input type

Current input

Scale range

  input (unipolar)

0~20mA;4~20mA

Data word format

Unipolar, full range

032000

Input resolution

Resolution

0.000625 mA020mA

0.0005 mA420mA


Accuracy of measurement

0.1%

Input impedance

250 Ω

Common mode voltage


120V AC

Common mode rejection

90dB, 60Hz @ DC

Input filter attenuation

3db @ 325 HZ

Diagnostic procedures

+24VDC power indicator, on: module power supply is normal,

Off: The module has no power supply, and all channel data becomes 32766

The dialing switch is set incorrectly, and all channel data becomes 32767

Field site - logic

500V AC

Field site - DC 24V

500V AC

DC 24V -- logic

500V AC

Addressing mode

VW addressing




Installation

Range selection and software configuration

[Range selection switch position]

6364887220780468757996311.png


[Range selection]

The following table shows how to set the range of the SM231 8AI module with the DIP switch. Switches 1, 2 and 3 can select the analog input range. All inputs are set to the same analog input range. In the following table, ON means connection and OFF means no connection. It is important to note that unused DIP switches SW4 ~ SW6 must be set to the OFF position.

Single polarity

Full scale input

Resolution 

SW1

SW2

SW3

OFF

OFF

OFF

0-20mA

 0.000625mA

OFF

ON

4-20mA

 0.0005mA


[Software Configuration]

For the SM231 8AI× 16-bit analog input module, its reading is in VW, not AIW, the relative position of the module is different, the corresponding address is different. The address calculation formula is as follows:

X (VWx) = slot number × 64 + input channel number × 2

The slot number corresponds to the module's installation location, with the first extension slot next to the CPU being 0, the second extension slot being 1, and so on. There are 8 input channels, from A to G, and the corresponding numbers are 0 to 7.

VWxx

Channel 0

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Slot 0

VW0

VW2

VW4

VW6

VW8

VW10

VW12

VW14

Slot 1

VW64

VW66

VW68

VW70

VW72

VW74

VW76

VW78

Slot 2

VW128

VW130

VW132

VW134

VW136

VW138

VW140

VW142

Slot 3

VW192

VW194

VW196

VW198

VW200

VW202

VW204

VW206

Slot 4

VW256

VW258

VW260

VW262

VW264

VW266

VW268

VW270

Slot 5

VW320

VW322

VW324

VW326

VW328

VW330

VW332

VW334

Slot 6

VW384

VW386

VW388

VW390

VW392

VW394

VW396

VW398

Note:  Because the offset address of Td2X text display is also in VW0, so If you need to use Td2X text display in your system, please don’t put the EM231 8AI×TC module in slot 0, or the td2X will not work normally. SIEMENS TD200 text displayer is same as TD2X.(SIEMENS is the trademark of SIEMENS AG.)